Heat release rate: a brief
primer
|
...by Dr. Vytenis
Babrauskas, Fire
Science and Technology Inc.
|
Background
|
When the aftermath of a serious fire is being investigated, one
of the most common questions is: Why did the fire get so large? Until
relatively recently, the 'large' questions could only be answered qualitatively,
since means of quantifying a fire size in engineering units did not exist.
Eventually, it was recognized that since heat is the energy output of the fire,
and scientific means exist for measuring energy, the problem may be soluble. The
principles are clear. Heat is measured in units of Joules. What is usually more
of interest is the rate at which heat is released, not the total amount. The
heat release rate (HRR) can thus be measured in Joules per second, which is
termed Watts. Since a fire puts out much more than 1 Watt, it is usually
convenient to quantify the HRR in kilowatts (1000 W) or megawatts (a million
watts).
|
Bench-scale measurement of HRR
|
Prior to the 1970s, such ideas, while theoretically accessible,
were not usable, since actual means of measuring HRR from fires were not
available. The first instruments for HRR measurement started being available in
the 1970s and they were bench-scale devices. (One specialized unit had been
already built in the 1950s in one lab.) Bench-scale means such instruments can
measure samples on the order of a few inches or a few centimeters in size, but
not real objects that could be man-sized (or even warehouse-sized). The early
HRR instruments (OSU apparatus, developed by Prof. Ed. Smith; NBS-I calorimeter,
developed by Alex Robertson and Bill Parker; etc.) suffered from normal
first-generation issues of usability and cost. The NBS-II calorimeter, for
instance, cost NIST $250,000 to build in 1977-78 (actual 1977 dollars). Shortly
after joining NIST in 1977, I was tasked to find a better way. Several years of
exploration elapsed, and by 1982 I had invented the Cone Calorimeter,
in its first iteration. This has since become the world standard, available at
test laboratories around the globe.
|
Furniture calorimeters (large-scale products
calorimeters)
|
Having a bench-scale HRR apparatus is not enough for
comprehensive studies of fires. In many cases, it is necessary to study the HRR
of objects in their full scale, or at least nearly full-scale. This development
was also started around 1979, and by 1982 two different apparatuses were
independently invented. The NIST furniture calorimeter was developed by myself,
along with Doug Walton, Randy Lawson, and Bill Twilley. The FMRC products
collector was developed by Gunnar Heskestad. These have also now become used
around the world and are the basis of numerous standards of ASTM, NFPA, and
other organizations.
|
Room calorimeters
|
The final HRR measuring apparatus which was needed was a room
calorimeter. Furniture calorimeters can measure the HRR of discrete objects,
able to support themselves on the floor. This does not include such products as
ceiling tiles nor wallboard. Also, special measuring issues arise when one wants
to measure a whole burning room, fully furnished. For such studies, room
calorimeters were needed. Room calorimeters were developed in a parallel effort
between Fred Fisher and Prof. Brady Williamson at UC Berkeley and by Billy Lee
and Jin Fang at NIST. This effort was also largely completed in 1982, meaning
that instruments of all three needed scales became available nearly
simultaneously in 1982.
|
Which scale to use?
|
It is costlier and more difficult to test in larger-scale
instruments, thus it would seem that preference would always go towards running
a bench-scale test. This is not necessarily true, since to make intelligent use
of the bench-scale data one needs a predictive model. In other words, it
is not of much interest to know what a 10 cm size sample would do; what is of
interest is the full-scale behavior of a piece of furniture, appliance, wall
covering, or even a whole room. For some categories of objects, such models have
been developed. These include upholstered furniture, wall linings, carpets, and
some others. But the available categories are few, while the types of objects
which can potentially be of interest in fire reconstructions are numerous. Thus,
one of the things which must first be determined is whether it is reasonable to
run bench-scale tests or whether full-scale testing is needed. We may note that
for polymer manufacturers and others developing new materials, it is often
sufficient to only use bench-scale testing. This is because they mainly wish to
find the relative differences in fire behavior, while actual product performance
may not be relevant to them since they do not even make the end
product.
|
The overwhelmingly important role of HRR in
fires
|
| HRR is not just 'one of many' variables used to describe a fire.
It is, in fact, the single most important variable in describing fire hazard.
(The only notable exception is for explosions). There are three main reasons for
this.
1. HRR is the driving force for fire.
The HRR can be viewed as the engine driving the fire. This tends
to occur in a positive-feedback way: heat makes more heat. This does not occur,
for instance, with carbon monoxide. Carbon monoxide does not make more carbon
monoxide.
2. Most other variables are correlated to HRR
The generation of most other undesirable fire products tends to
increase with increasing HRR. Smoke, toxic gases, room temperatures and other
fire hazard variables generally march step-in-step with HRR as HRR
increases.
3. High HRR indicates high threat to life.
Some fire hazard variables do not relate directly to threats to
life. For instance, if a product shows very easy ignitability or high flame
spread rates, this does not necessarily mean that fire conditions are expected
to be dangerous. Such behavior may merely suggest a propensity to nuisance
fires. High HRR fires, however, are intrinsically dangerous. This is because
high HRR causes high temperatures and high heat flux conditions, which may prove
lethal to occupants.
|
If HRR is so important, why are regulators not
regulating it?
|
In the US, over the last decade, HRR has shown up in various
regulations and specifications, but this has been in specialized areas. Where it
has not yet shown up in is in the building codes. The US model building codes
still regulate products according to the Steiner Tunnel Test. This test was
developed during the late 1930s and early 1940s and, of course, predates all of
modern fire protection engineering knowledge. The test controls flame spread
which is not, as noted above, a primary factor in determining human
untenability. Over the years, a number of research projects documented various
shortcomings of this test. The basic reason why we have not yet progressed
beyond 1940s technology in the building codes has to do with the inertia of the
process and of the lack of funding resources necessary to propel a building code
change. In the US, there is no public-interest organ with specific funding to
conduct research leading to building code improvements. Changes, instead, are
usually originated by commercial entities. As of now, no commercial group has
decided that it would be advantageous for them to sponsor a change, intended to
introduce improved engineering methods in this area. In fire litigation however,
HRR testing is well established, and eventually it is also certain to become
utilized in building codes.
|
Some common misconceptions
|
- We have taken measures to control the ignitability, so we
don't have to worry about HRR
It is certainly wise to always control ignition sources and also
to use less ignition-prone materials, when possible. Such a strategy, however,
can never be relied upon to avoid an ignition. Neither HRR nor any other
consequences of fire will come into play as long as there is no ignition.
However, when an ignition does occur, limiting the HRR means that the fire has a
chance to be controllable and not disastrous.
One must also realize that if the application is not in aircraft
safety, military or NASA areas, the affordable, commercial materials that are
available are not very ignition resistant. Studies have shown that even small
ignition sources normally apply about 35 kW m2 heat flux to
their target. If one then seeks materials able to resist an ignition flux of 35
kW m2, one finds that these are rare and costly.
- Coroners tell us that inhalation of toxic fire gases is
the main cause of fire deaths, so we should control toxicity, not
HRR
This fallacy rests on the imprecise definition of the term
'toxicity.' Regulatory officials sometimes presume that this means that 'toxic
potency' is the root problem and that this is what must be controlled. Toxic
potency is the toxicologist's term for defining how toxic is the substance
when you inhale 1 gram of it. But of course the victim will inhale something
other than 1 g of it. How much of the substance will be inhaled is
governed by the fire's mass loss rate. The mass loss rate is closely
proportional to the HRR of the fire. Now, what is important to realize is that
studies at NIST and elsewhere have shown that for commercial products, burned
under realistic fire conditions, toxic potencies vary only within a narrow band.
By contrast, mass loss rates (same as HRR) vary over an enormous range among
products of any given type. Since both toxic potency and mass loss rate affect
the total impact of the fire on the victim, it is clear that effective control
can be mounted by limiting mass loss rates, but there is little that can be
achieved by attempting to control toxic potencies.
For further reading, see the textbook Heat Release in
Fires.
|
| This article © Copyright 1996 by Vytenis
Babrauskas.
|
|